Description

Protected escape routes allow occupants to move from occupied areas to a place of safety before smoke, heat or fire compromises tenability. In wildfire-prone areas they must remain usable during external smoke exposure, ember attack, power loss and wider emergency evacuation.

For offices and commercial buildings, the design should consider high and variable occupant loads, visitors unfamiliar with the building, vulnerable users and the possibility of phased or simultaneous evacuation.

Image

Please download the PDF to have the information sent directly to your email address.

Healthcare Waste Insulation

Download pdf

Send download link to:

I have read and I accept the Privacy policy

Implementation Guide

  • Determine occupant load, evacuation strategy and exit capacity using the applicable national fire code
  • Provide independent alternatives where required and connect occupied areas to protected stairs, corridors or final exits
  • Minimise dead ends and excessive travel distances and verify final limits against building use and compartmentation
  • Integrate emergency lighting, illuminated wayfinding and smoke-control measures where required
  • Keep routes free of storage, combustible displays and temporary obstructions
  • Provide accessible evacuation arrangements for persons with reduced mobility
  • Test the evacuation plan and coordinate it with wildfire warnings and civil-protection instructions

Benefits and Limitations

Benefits

  • Provides a clear and protected path to safety
  • Reduces exposure to smoke, heat and panic
  • Supports fire-service intervention and rescue
  • Can remain functional during loss of normal lighting
  • Improves overall life-safety resilience

Limitations

  • Does not prevent wildfire exposure or building damage
  • Depends on doors, lighting, signage and smoke-control systems remaining operational
  • Crowding can occur if occupant loads are underestimated
  • Retrofit can require major layout changes
  • External conditions beyond the final exit may still be unsafe

Parameter and data

Application: Offices, retail buildings, shopping centres, public buildings and other commercial occupancies in wildfire-prone areas

Construction Solutions: Protected corridors, enclosed stairs, fire-resistant doors, smoke lobbies where required, final exits and refuge areas

Travel Distance: Project-specific and code-dependent. The 20-45 m range in the draft should be treated only as indicative background

Fire Resistance: Defined by building height, use and fire strategy; EI 60-EI 120 is common in many applications but national rules govern

Smoke Protection: Smoke-resistant doors, smoke lobbies, stair pressurisation or smoke ventilation where required

Emergency Lighting / Signage: EN 1838, EN 50172 and EN ISO 7010 where applicable

Expected Service Life: Primary construction: building lifetime; lighting, doors, controls and signage require earlier renewal

Maintenance: Inspection of exits, doors, signage, emergency lighting, compartmentation and smoke-control interfaces

Indicative Regulatory References: Regulation (EU) 2024/3110 (CPR) where relevant; EN 1838; EN 50172; EN ISO 7010; EN 1125 / EN 179 where applicable; national fire and accessibility regulations

Please download the PDF to have the information sent directly to your email address.