Description
Solar chimneys are vertical or inclined shafts that use solar-heated air to strengthen the stack effect and extract warm indoor air.
Solar radiation heats an absorber surface inside the chimney, increasing air temperature and buoyancy. This creates upward airflow and draws replacement air from lower openings or cooler shaded zones, supporting passive ventilation and heat removal during hot periods.
Image

Please download the PDF to have the information sent directly to your email address.
Healthcare Waste Insulation
Send download link to:
Implementation Guide
- Locate the chimney in an area with strong solar exposure
- Define shaft height, cavity depth and inlet/outlet areas through airflow calculations
- Use absorptive internal surfaces to increase buoyancy
- Provide shaded or cooler low-level air inlets
- Include controllable vents or dampers where seasonal control is required
- Ensure access for cleaning and inspection
Benefits and Limitations
Benefits
- Increases natural ventilation without continuous fan energy
- Supports passive heat extraction during hot periods
- Can improve night purge and indoor air movement
- Works well with courtyards, earth tubes and shaded air intakes
- Requires relatively low operational energy
Limitations
- Performance depends strongly on solar radiation and chimney height
- Less effective when outdoor air is very hot or humid
- May be insufficient during still or very warm nights
- Requires careful fire, acoustic and rain detailing
- Poorly designed air paths can limit airflow
Parameter and data
Design: Solar-heated vertical shaft designed to create buoyancy-driven airflow and enhance natural ventilation. Chimney height, cavity depth, inlet/outlet areas and air-path resistance should be coordinated to maximize stack pressure while limiting pressure losses
Materials and Components:
- Glazing or translucent cover
- Dark metal or masonry absorber
- Insulated shaft
- Dampers or controllable vents
- Insect screens
- Rain protection
- Actuators where automated control is used
Application: Naturally ventilated or mixed-mode buildings, including schools, offices, residential buildings, atria and selected healthcare support areas
Technical Properties:
- Air gap: Commonly around 100–500 mm
- Height: Should be maximized where feasible to increase stack pressure
- Inlet and outlet areas: Sized according to required airflow and allowable pressure losses
Relevant properties include: Buoyancy-driven ventilation, passive heat extraction, night-purge support and natural airflow amplification
Thermal / Cooling Performance: Provides medium–high passive ventilation and heat-extraction potential. Performance depends mainly on solar radiation, chimney height, absorber temperature, inlet/outlet geometry, air-path resistance and outdoor temperature
Operation: Passive, manually controlled or automated, the chimney can operate solely through stack effect or incorporate controllable dampers and, where necessary, hybrid fan assistance
Advantages: Provides passive airflow amplification and heat extraction using solar energy, with low operational energy demand and good compatibility with other passive cooling measures
Maintenance: Low–Medium: Periodic inspection of vents, dampers, glazing, seals, drainage and insect screens. Automated systems also require inspection of actuators and controls
Environmental Impact: Low–Medium: Operational energy use is very low, while environmental impacts mainly come from glazing, structural materials and any automated controls
Applicability Criteria: Most suitable for buildings with good solar exposure, sufficient vertical height, a clear low-resistance airflow path, access to shaded or cooler replacement air. Less suitable where outdoor air remains hotter than indoor air for long periods or where acoustic, fire or airtightness constraints prevent sufficient airflow
Expected Service Life: Shaft and structural components: Approximately 30–50+ years. Dampers and actuators: Approximately 10–20 years