Description
Earth tubes, also known as ground-air heat exchangers, precondition outdoor ventilation air by passing it through buried ducts where the surrounding soil remains more thermally stable than outdoor air.
During summer and heatwaves, warm outdoor air transfers heat to the cooler ground before entering the building or ventilation system, reducing supply-air temperature and peak cooling demand.
Image

Please download the PDF to have the information sent directly to your email address.
Healthcare Waste Insulation
Send download link to:
Implementation Guide
- Assess soil temperature, thermal conductivity, groundwater level and available external area
- Define burial depth, duct length, diameter and airflow through thermal and pressure-drop calculations
- Use airtight, smooth and cleanable ducts
- Provide continuous slope and reliable condensate drainage
- Install filters and protected outdoor air intakes
- Provide inspection and cleaning access throughout the system
Benefits and Limitations
Benefits
- Reduces outdoor-air temperature before it enters the building
- Can reduce peak cooling demand
- Uses relatively little operational energy when pressure losses are controlled
- Can work with passive or hybrid ventilation
- Benefits from stable ground temperatures during extreme heat
Limitations
- Requires significant excavation and external space
- Performance depends strongly on soil and groundwater conditions
- Condensation and hygiene risks require careful design
- Radon or contaminated soils can limit applicability
- Retrofit installation can be difficult in dense urban sites
Parameter and data
Design: Buried air-duct system designed to exchange heat between ventilation air and the surrounding ground. Depth, length, diameter and airflow should be defined according to soil conditions, required ventilation rate, heat-transfer performance and acceptable pressure drop
Materials and Components:
- HDPE or PP ducts
- Concrete or coated-steel ducts where appropriate
- Outdoor air intake cowls
- Filters
- Inspection chambers
- Condensate drains
- Fans where mechanical assistance is required
Application: Buildings with available external land, including schools, offices, healthcare support buildings, low-rise residential buildings and emergency facilities
Technical Properties:
- Burial depth: Approximately 1.5–3.0 m
- Duct length: Commonly 20–60 m
- Duct diameter: Approximately 150–600 mm, depending on airflow requirements
Thermal / Cooling Performance: Provides medium–high pre-cooling potential. Supply-air temperature reductions of several degrees may be achievable, but actual performance depends strongly on soil temperature, soil thermal conductivity, burial depth, duct length, airflow rate and outdoor conditions
Operation: Passive or fan-assisted, the system can operate passively when connected to wind- or stack-driven ventilation, or mechanically when integrated into an AHU or ventilation system
Advantages: Uses the relatively stable temperature of the ground to reduce ventilation-air temperature and peak cooling loads with low operational energy
Maintenance: Medium: Periodic filter replacement, inspection of condensate drainage, hygiene checks and cleaning of ducts and inspection chambers
Environmental Impact: Medium: Excavation and buried duct materials create construction impacts, while reduced cooling demand and low operational energy can provide lifecycle benefits
Applicability Criteria: Most suitable where sufficient external land is available and soil and groundwater conditions are favourable. The system should be avoided or carefully assessed where there are contaminated soils, elevated radon risk, high groundwater, poor drainage and limited access for maintenance
Expected Service Life: 30–50 years for the buried duct system, provided that ducts remain accessible, dry, airtight and protected. Filters, drainage components and mechanical equipment may require earlier replacement