Description

Fire-resistant doors are certified assemblies that limit fire, smoke and heat transfer between compartments for a defined period. They are critical at protected corridors, stairwells, lobbies, technical rooms and high-risk areas.

In wildfire-prone buildings they can contain internal fires initiated by ember entry or exterior ignition. Performance depends on the complete assembly remaining in its tested configuration.

Image

Please download the PDF to have the information sent directly to your email address.

Healthcare Waste Insulation

Download pdf

Send download link to:

I have read and I accept the Privacy policy

Implementation Guide

  • Select the required EI2/EW/E and smoke-control performance
  • Install the complete certified assembly with compatible frame, seals, fixings, threshold and hardware
  • Provide self-closing devices where required and panic hardware on escape routes
  • Use hold-open devices only where automatically released by the fire alarm and permitted by the tested configuration
  • Maintain correct gaps and ensure door leaves close fully
  • Protect doors against impact and misuse
  • Inspect and record condition at planned intervals

Benefits and Limitations

Benefits

  • Contains fire and smoke between compartments
  • Protects escape routes and stairs
  • Provides additional evacuation time
  • Supports firefighter intervention
  • Integrates into normal circulation without active energy when closed

Limitations

  • Depends on the door being closed and correctly latched
  • Damaged seals or hardware reduce performance
  • Heavy doors can create accessibility issues
  • Hold-open devices add maintenance
  • Retrofit may require wall/frame modification

Parameter and data

Application: Fire compartments, protected corridors, stairwells, lobbies, technical rooms, basements and storage

Construction Solutions: Hinged, sliding, glazed or smoke-control fire doors; self-closing and hold-open configurations where certified

Materials: Steel, fire-rated timber, aluminium fire-rated systems, mineral cores, fire-resistant glazing and intumescent seals

Fire Resistance: Common classifications include EI2 30, 60, 90 and 120 depending on the project requirement

Smoke Control: Sa or S200 where smoke leakage control is required

Expected Service Life: Approximately 20-40 years with correct use and maintenance

Maintenance: Closing function, gaps, hinges, locks, panic hardware, seals, glazing and hold-open devices

Indicative Regulatory References: EN 13501-2; EN 16034; EN 1634-1 / EN 1634-3; EN 1125; EN 179; national fire-safety regulations