Description
Beam smoke detectors use a projected optical beam across a large space to detect smoke attenuation. They are suited to high, open volumes where installing and maintaining many point detectors is difficult.
They can be effective in warehouses, atria and logistics buildings, but alignment, structural movement and smoke stratification must be addressed.
Image

Please download the PDF to have the information sent directly to your email address.
Healthcare Waste Insulation
Send download link to:
Implementation Guide
- Use beam detection primarily in large open spaces with clear line of sight
- Assess ceiling height, roof geometry and smoke stratification
- Avoid beam paths that may be obstructed by storage, cranes or banners
- Provide stable mounting and alignment compensation
- Ensure safe access for testing and maintenance
- Integrate alarm and fault signals with the main fire alarm
- Recommission after major layout or structural changes
Benefits and Limitations
Benefits
- Large-area coverage with relatively few devices
- Useful in high spaces
- Can reduce wiring and installation density
- Integrates with standard fire alarm systems
- Suitable for warehouses and atria
Limitations
- Requires clear line of sight
- Building movement can cause misalignment
- Smoke stratification can delay response
- Poor fit for subdivided spaces
- Later obstructions can compromise coverage
Parameter and data
Application: Warehouses, atria, sports halls, hangars, logistics buildings and other large open volumes
Detection Principle: Attenuation of an optical beam by smoke between transmitter/receiver or reflector
Coverage: Project-specific according to detector specification and geometry
Mounting: Rigid support with allowance for thermal/structural movement
Expected Service Life: Typically 10-15+ years with maintained alignment and electronics
Maintenance: Optical cleaning, alignment verification and functional testing
Indicative Regulatory References: EN 54-12 for line-type smoke detectors where applicable; national fire detection and alarm design rules